Practice Mechanical Journeyman Untimed (Dark Theme)

Report a question

You cannot submit an empty report. Please add some details.

Practice Mechanical Journeyman Untimed (Dark Theme)

Practice Mechanical Journeyman Untimed

1 / 50

1. Tests performed by                       may be required by the code official where there is insufficient evidence of code compliance.

2 / 50

2. Mechanical systems in structures located in flood hazard areas shall be located at or above the

                                  .

3 / 50

3. Notches on the ends of solid wood joists shall not exceed                         percent of the joist depth.

4 / 50

4. Cooling towers and fluid coolers shall be provided with _____________.

5 / 50

5. Appliances installed in pits or excavations shall not come in __________ contact with the surrounding soil and shall be installed not less than 3 inches (76mm) above the pit floor

6 / 50

6. Vented wall furnaces shall not circulate air from _________ to other parts of the building.

7 / 50

7. The required ventilation opening into a sauna room shall be a minimum of _____ inches by ______ inches and located near the top of the door.

8 / 50

8. One set of construction documents shall be kept                               until completion of the project.

9 / 50

9. The code official has the authority to grant modifications to the code __________.

10 / 50

10. Where roof-mounted solar collectors serve as the roof covering, the use of plastic solar collectors is exempt from the building code’s general roof covering requirements if the collector cover meets the requirements for                          .

11 / 50

11. Where natural ventilation is used, the maximum rated output capacity of hydrogen generating appliances shall not exceed 4 standard cubic feet per minute of hydrogen for each                          square feet of floor area.

12 / 50

12. Where natural ventilation is used, indoor locations intended for hydrogen-generating operations shall communicate with the outdoors through openings with a minimum cross-sectional dimension of                 Inches

13 / 50

13. At an underground inspection where the excavated soil contains rocks, broken concrete or rubble,                            is required on the job site.

14 / 50

14. Roof-mounted solar collectors that serve as the roof covering shall conform to the requirements of the                for roof coverings.

15 / 50

15. The flash point of heat transfer fluids used in solar systems in Group F or H occupancies shall not be lower                                .

16 / 50

16. Ducts shall have a minimum slope of ________ inch per foot to allow drainage to a point provided with access.

17 / 50

17. Other than on the control side, a minimum clearance of ___ inches is required on all sides of a floor furnace.

18 / 50

18. Pressurized thermal water storage tanks shall be listed and labeled, with the label required to indicate all of the following information, except the                         .

19 / 50

19. Cuts, notches and bored holes are prohibited in structural composite lumber, except where

                                  .

20 / 50

20. Cooking appliances installed within areas where domestic cooking operations occur shall be listed and labeled as _________-type appliance for domestic use.

21 / 50

21. Appliances shall not be installed in a location where they may be subject to mechanical damage unless they are                              .

22 / 50

22. A                   shall not be used as a heat transfer fluid in a solar system

23 / 50

23. Ducts utilized in solar heating shall have sufficient thermal insulation to limit the exposed surface temperature to                   ˚F.

24 / 50

24. Equipment and appliances in solar thermal systems shall be installed in accordance with the                   .

25 / 50

25. Oil-fired floor furnaces shall be tested in accordance with UL _____________.

26 / 50

26. Roof and wall penetrations shall be flashed and sealed to prevent entry of                       .

27 / 50

27. When calculating free area for required natural ventilation openings serving indoor hydrogen-refueling operations, it can be assumed that wood louvers will have                        percent free area.

28 / 50

28. ______________ occupancy occurs where two or more occupancies are are located within the same building.

29 / 50

29. A permit is not required for a self-contained refrigeration system that contains a maximum of                                         pound(s) of refrigerant.

30 / 50

30. Listed and labeled hearth extensions for factory-built fireplaces, fireplace stoves and solid-fuel-type room heaters shall comply with ____________

31 / 50

31. The IFGC regulates piping systems for natural gas with an operating pressure of _________ psig or less.

32 / 50

32. When the provisions of the FGC are applicable, a change of occupancy requires _____________.

33 / 50

33. Only in an emergency situation that poses an immediate hazard to life or property is the code official authorized to _______________.

34 / 50

34. Where the air-infiltration-rate is unknown, a room or space providing indoor combustion air requires a minimum volume of                            cubic feet per 1,000 Btu/h of the appliance input rating.

35 / 50

35. Which of the following individuals is not qualified to serve on the Board of Appeals for the IFGC?

36 / 50

36. Where mechanical exhaust interferes with the operation of an appliance,                         is required. (SHALL BE PROVIDED)

37 / 50

37. An installation is not required to be brought into compliance if it is _________ at the time of adoption of the code.

38 / 50

38. The permit or a copy shall be kept on the site of the work __________.

39 / 50

39. The maximum length of an electrical bonding jumper for a corrugated stainless steel tubing (CSST) system is                        feet.

40 / 50

40. Suspended mechanical equipment shall be installed a minimum of                   inches above the adjoining grade.

41 / 50

41. Catwalks installed to provide the required access to rooftop equipment shall be a minimum of                 inches wide.

42 / 50

42. Openings obtaining indoor combustion air from a different story require a total minimum free area of                          square inch(es) per 1,000 Btu/h of the total input rating of appliances.

43 / 50

43. Notching at the ends of wood joists shall not exceed                         the joist depth.

44 / 50

44. The code official has the authority to grant modifications to the code  ____________.

45 / 50

45. Unless otherwise approved in accordance with Section 105, appliances regulated by this code shall be              .

46 / 50

46. Conversion of an appliance to a different fuel gas is allowed if in accordance with the                      instructions.

47 / 50

47. Appliances shall not be installed in a location subject to vehicle damage except                          

48 / 50

48. Equipment and appliances having an ignition source shall                   in Group H Occupancies or control areas where open use, handling or dispensing of combustible,” flammable or explosive materials occurs.

49 / 50

49. Unlisted appliances                                .

50 / 50

50. The purpose of this code is to provide _____________ standards to safeguard life or limb, health, property and public welfare.

Your score is

Share your results with your friends

LinkedIn Facebook Twitter VKontakte

Leave a Comment