Practice Mechanical Journeyman Untimed (Dark Theme)

Report a question

You cannot submit an empty report. Please add some details.

Practice Mechanical Journeyman Untimed (Dark Theme)

Practice Mechanical Journeyman Untimed

1 / 50

1. In order for an alternative material, design or method of construction to be considered acceptable, it must be equivalent to the code based on all but which of the following criteria?

2 / 50

2. Grease duct systems serving type 1 hood, where enclosures are not required, shall have a clearance to combustible construction of not less than __________ inches

3 / 50

3. Cooling towers shall be located to prevent ________________ from entering occupied spaces.

4 / 50

4. Potable water supplies to solar systems shall be protected against contamination in accordance with the                    .

5 / 50

5. When a building permit is issued, the construction documents shall be stamped                                .

6 / 50

6. Floor furnaces shall be placed a minimum of ___________ inches from the nearest wall.

7 / 50

7. Studs used in nonbearing partitions are permitted to be cut or notched to a maximum depth of

                               percent of the stud depth.

8 / 50

8. Mechanical systems in structures located in flood hazard areas shall be located at or above the

                                  .

9 / 50

9. The location of cooling towers on the property shall be as required in accordance with the International _____________  Code.

10 / 50

10. Appliances shall not be installed in a location where they may be subject to mechanical damage unless they are                              .

11 / 50

11. Where natural ventilation is used, the maximum rated output capacity of hydrogen generating appliances shall not exceed 4 standard cubic feet per minute of hydrogen for each                          square feet of floor area.

12 / 50

12. Drains, overflows and blowdown provisions for cooling towers shall be _____________ connected to an approved disposal system.

13 / 50

13. The minimum flash point of the actual heat transfer fluid utilized in a solar system shall be           ˚F above the design maximum nonoperating temperature of the fluid attained in the collector.

14 / 50

14. Where a relief valve is required in a solar energy system, the valve shall be set at a maximum of            percent of the nameplate pressure rating.

15 / 50

15. The code official has the authority to __________ the provisions of the code.

16 / 50

16. At an underground inspection where the excavated soil contains rocks, broken concrete or rubble,                            is required on the job site.

17 / 50

17. Roof-mounted solar collectors that serve as the roof covering shall conform to the requirements of the                for roof coverings.

18 / 50

18. Unless the factory-built fireplace system has been specifically tested, listed and labeled for the installation, ____________ shall not be installed.

19 / 50

19. Provisions of an appendix do not apply unless                            .

20 / 50

20. Where the depth of an excavation housing an appliance exceeds 12 inches below the adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry extending a minimum of                                   inches above adjoining grade.

21 / 50

21. Every occupied space shall be ventilated by natural or ____________ means

22 / 50

22. Once a permit has expired because the authorized work was not commenced or was suspended/abandoned, a new permit may be issued at one-half the amount required for a new permit, provided the work has not been abandoned for more than                               .

23 / 50

23. Notches in the top or bottom of solid wood joists shall not be located in the middle                      of the span.

24 / 50

24. The board of appeals is not authorized to rule on an appeal based on a claim that                              .

25 / 50

25. A mechanical system that constitutes a fire or health hazard shall be declared                              .

26 / 50

26. Walls enclosing occupiable rooms where food is stored, served or sold shall be constructed to protect against the entrance of                           in accordance with the building code.

27 / 50

27. Vented wall furnaces shall be located so that a door swing maintains a minimum clearance of ______ inches from any air inlet.

28 / 50

28. Which of the following appliances must be tested in accordance with UL 730?

29 / 50

29. Appliances located in private garages and carports shall be installed with a minimum clearance of ___________ feet (1829 mm) above the floor.

30 / 50

30. The quality of water supplied to evaporative cooling equipment shall be in accordance with the ________.

31 / 50

31. Only in an emergency situation that poses an immediate hazard to life or property is the code official authorized to _______________.

32 / 50

32. Tests performed by  __________ may be required by the code official where there is insufficient evidence of code compliance.

33 / 50

33. The maximum length of an electrical bonding jumper for a corrugated stainless steel tubing (CSST) system is                        feet.

34 / 50

34. Holes bored in solid wood joists shall be located not less than                      inch(es) from the top and bottom joist.

35 / 50

35. If the permit has not been issued, an application for a permit is considered abandoned __________ days after the date of filing.

36 / 50

36. An automatic appliance shut-off device is required for condensate pumps located                              .

37 / 50

37. Unless otherwise protected from impact, appliances located in a public garage shall be installed a minimum of                       feet above the floor.

38 / 50

38. One set of construction documents shall be kept __________ while work is in progress.

39 / 50

39. Where an appliance is located in an attic, a                     is required at the access opening to the attic passageway.

40 / 50

40. The code official is authorized to accept reports of inspection by ____________.

41 / 50

41. Appliances in structures located in flood hazard areas shall be located at or above the                   .

42 / 50

42. Which of the following individuals is not qualified to serve on the Board of Appeals for the IFGC?

43 / 50

43. _________ provide supporting documentation to verify that an alternative material or assembly complies with the intent of the code.

44 / 50

44. Where a screen is installed at a combustion air opening, the mesh size shall not be smaller than                      inch.

45 / 50

45. Catwalks installed to provide the required access to rooftop equipment shall be a minimum of                 inches wide.

46 / 50

46. Appliances having an ignition sources shall be elevated such that the ignition source is not less than                   inches above the floor in a private garage.

47 / 50

47. Where a reduction in clearance to combustible materials is permitted, the side clearance for an appliance is permitted to be reduced from 12 inches to a minimum of              inches by installing No. 24 gage galvanized sheet metal with a ventilated air space

48 / 50

48. In bearing partitions, any wood stud is permitted to be cut or notched to a depth not exceeding                                  percent of its width.

49 / 50

49. When installed in a bedroom, a single wall-mounted unvented room heater is limited to an input rating not greater than                                  Btu/h.

50 / 50

50. Notches in the flange of a cold-formed steel stud in a bearing wall                               

Your score is

Share your results with your friends

LinkedIn Facebook Twitter VKontakte

Leave a Comment